Heat and Cooling in VFD Panels
How much heat a drive gives off, and how to get it out of the panel.
Choose the enclosure by where the panel will live. NEMA 1 suits clean, dry indoor rooms. NEMA 3R is for outdoor sites with rain, sleet and ice. NEMA 4 adds protection against windblown dust and hose-directed water. NEMA 4X is Type 4 plus corrosion resistance, usually stainless steel or non-metallic, for wet or chemical areas.
Most of the panels we build use one of these four types. Each step up adds protection, and cost.
The table shows what each type is built to resist. If a location calls for more than one, choose the type that covers all of them.
| NEMA 1 | NEMA 3R | NEMA 4 | NEMA 4X | |
|---|---|---|---|---|
| Indoor use | Yes | Yes | Yes | Yes |
| Outdoor use | No | Yes | Yes | Yes |
| Falling dirt | Yes | Yes | Yes | Yes |
| Rain, sleet, snow | No | Yes | Yes | Yes |
| Windblown dust | No | No | Yes | Yes |
| Hose-directed water | No | No | Yes | Yes |
| Corrosion resistance | No | No | No | Yes |
| Typical material | Painted steel | Painted steel | Painted steel | Stainless or non-metallic |

Electrical rooms and clean control rooms usually only need NEMA 1. Outdoor pump stations and skids on Texas sites usually need NEMA 3R as a minimum, and NEMA 4 where equipment is washed down or exposed to blowing dust.
Water treatment plants, chemical feed areas and coastal sites often call for NEMA 4X, because chlorine, caustic and salt air attack painted steel. Stainless steel or a non-metallic enclosure lasts far longer in those places.
Sealing a panel to NEMA 4 or 4X keeps water out, but it also keeps heat in. Drives and power supplies may need an air-to-air heat exchanger or an enclosure air conditioner instead of filter fans, because fans and vents would break the seal.
Every hole for an HMI, a pushbutton or a cable entry must keep the enclosure's rating. We use operators, glands and fittings rated for the same type as the enclosure, so the panel is still NEMA 4 or 4X once it is fitted out.

NEMA 4X has all the protection of NEMA 4 against hose-directed water, windblown dust and rain, plus resistance to corrosion. It is usually stainless steel or non-metallic.
No. NEMA 1 is for indoor use only. Outdoor panels need at least NEMA 3R.
No. It keeps out falling rain, sleet and snow, but it is not built for hose-directed water. Use NEMA 4 or 4X where panels are hosed down.
No. The types in this guide are for general-purpose locations. Hazardous locations need different enclosures and equipment.
Mostly NEMA 1 for clean indoor rooms, NEMA 3R for outdoor sites, NEMA 4 for hose-down areas and NEMA 4X where corrosion is a concern. Tell us where the panel will be installed and we will recommend a rating.